- Mains supply :230V 50/60Hz.
- Mains rated Current :350mA maximum.
- Internal power supply : 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
- Total output current limited : to 1.5A @ 230Vac (ImaxA eq 146mA).
- Quiescent current :25mA (mains failed, internal sounder active, PSU & gen fault LED lit)
- Alarm voltage :27V max, 20V min (final battery voltage).
- Max battery size and type :2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
- No. of detector zone circuits :8 (Max. length per circuit is 500m).
CFP708-4/CON 8 ZONE PANEL CONTEXT PLUS
CFP 8zone conventional fire alarm panel offers an array of user and installer-friendly
features at a very competitive price.
Supplied in an attractive flush or surface mountable plastic enclosure, it includes eightdetector zones, four conventional
sounder circuits, class change and alert inputs, on-board fire and fault relays and combined keypad/keyswitch entry.
A wide range of engineering functions are also provided including selectable zone delays, coincidence and non-latching
zone facilities. Comprehensive test and fault finding facilities are also provided.